| |
Click on Fire
Test thumbnails below for enlarged views |
| |
MSC/Circular 913
contains the IMO Guidelines and test procedures for the approval of fixed,
water-based, local application, fire-fighting systems for use in Category A
machinery spaces and Scotch Mist has been tested against this rigorous
standard. |
| |
|
| |
The enclosure used for carrying out the tests is a
massive 10 metres square with an overall height of 6 metres. It is sufficiently
large and provided with adequate natural ventilation during the fire test to
ensure that the oxygen concentration at the fire location during tests remains
above 20% without activation of the local application fire-fighting
system. The fire scenarios consist of
nominal 1 and 6 Megawatt spray fires, produced using light diesel oil fueled by
pressurised diesel jets |
| |
|
| |
The tests are
intended to evaluate the fire-extinguishing capabilities of individual nozzles
and grids of nozzles used as local application fire-fighting systems on light
diesel oil fuel spray fires. The tests also define the following design and
installation criteria:
- Maximum spacing between
nozzles
- Minimum and maximum distance
between the nozzles and the protected hazard
- The need for nozzles to be
positioned outside of the protected hazard
- Minimum and maximum operating
pressure.
The local application
system consists of uniformly spaced nozzles directed vertically downward using
a 2 x 2 nozzle grid, installed 1 m below the ceiling of the enclosure, the
maximum spacing of the nozzles being in accordance with the Scotch Mist design
and installation manual. |
| |
|
| |
The
fire-extinguishing capabilities of the system are evaluated for minimum and
maximum separation distances (the distance between the nozzle grid and the fuel
spray nozzle), as defined in the Scotch Mist design and installation manual.
Each separation distance is evaluated against the two fire scenarios (1 and 6
MW spray fires).
Tests are conducted
with the fuel spray nozzles horizontally positioned in the following
locations:
- Between four nozzles
- Under one nozzle at the edge of
the grid
- Between two nozzles at the edge
of the grid.
|
| |
|
| |
The local
application fire-fighting system is required to extinguish the test fires
within 5 minutes from the start of water discharge. If the fire re-ignites
after this five minute water discharge period, the test is considered to be a
failure. Scotch Mist extinguished the test fires within the prescribed time,
many within a matter of seconds, obtaining a PASS result for all
tests.
Click here to download a small 300kb
movie |
| |
|
| |
Go to top of
page |